Description
| Control output | Relay (250VAC~ 3A) or SSR drive (12VDC |
|---|---|
| Option output | Alarm 1/2 |
| Power supply | 100-240VAC~ 50/60Hz |
| Approval | |
| Display accuracy_RTD | •At room temperature(23ºC ± 5ºC):(PV ± 0.5% or ±1ºC, select the higher one) ± 1-digit •Out of room temperature range:(PV± 0.5% or ±2ºC, select the higher one)± 1-digit |
| Display accuracy_Thermocouple | •At room temperature(23ºC ± 5ºC):(PV ± 0.5% or ±1ºC, select the higher one) ± 1-digit •Out of room temperature range:(PV± 0.5% or ±2ºC, select the higher one)± 1-digit |
| Hysteresis(adjustable sensitivity) | 1 to 100℃/℉(0.1 to 50.0℃/℉) variable |
| Proportional band | 0.1 to 999.9℃/℉ |
| Integral time | 0 to 9999 sec |
| Derivative time | 0 to 9999 sec |
| Control period | 0.5 to 120.0 sec |
| Manual reset | 0.0 to 100.0% |
| Environment_Ambient temperature | -10 to 50℃, storage: -20 to 60℃ |
| Environment_Ambient humidity | 35 to 85% RH, storage: 35 to 85% RH |
| Insulation type | Double insulation or reinforced insulation(mark: |
| Weight | Approx. 194g(approx. 122g) |
※In case of the AC voltage model, SSR drive output method (standard ON/OFF control, cycle, control, phase control) is available to select.
※Display accuracy: Thermocouple L(IC) type, RTD Cu50Ω
•At room temperature (23℃ ±5℃): (PV ±0.5% or ±2℃, select the higher one) ±1-digit
•Out of room temperature range: (PV ±0.5% or ±3℃, select the higher one) ±1digit
In case of TC4SP Series, ±1℃ will be added.
※The weight includes packaging. The weight in parenthesis is for unit only.
※Environment resistance is rated at no freezing or condensation.