TC4Y-14R

TEMP.ERATURE CONTROLER 48X72 RELAY + SSR

Size DIN W72×H36mm
Display method 4-digit 7-segment LED
Control method ON/OFF control, P, PI, PD, PID control
Input specification Thermocouple: K(CA), J(IC), L(IC)
RTD: DPt100Ω, Cu50Ω
Sampling cycle 100ms

Datasheet

Control output Relay (250VAC~ 3A) or SSR drive (12VDC ) [ON/OFF, phase, cycle]
Option output Alarm 1
Power supply 100-240VAC~ 50/60Hz
Approval  
Display accuracy_RTD •At room temperature(23ºC ± 5ºC):(PV ± 0.5% or ±1ºC, select the higher one) ± 1-digit
•Out of room temperature range:(PV± 0.5% or ±2ºC, select the higher one)± 1-digit
Display accuracy_Thermocouple •At room temperature(23ºC ± 5ºC):(PV ± 0.5% or ±1ºC, select the higher one) ± 1-digit
•Out of room temperature range:(PV± 0.5% or ±2ºC, select the higher one)± 1-digit
Hysteresis(adjustable sensitivity) 1 to 100℃/℉(0.1 to 50.0℃/℉) variable
Proportional band 0.1 to 999.9℃/℉
Integral time 0 to 9999 sec
Derivative time 0 to 9999 sec
Control period 0.5 to 120.0 sec
Manual reset 0.0 to 100.0%
Environment_Ambient temperature -10 to 50℃, storage: -20 to 60℃
Environment_Ambient humidity 35 to 85% RH, storage: 35 to 85% RH
Insulation type Double insulation or reinforced insulation(mark: , dielectric strength between the measuring input part and the power part: AC power 2kV, AC/DC Power 1kV)
Weight Approx. 174g(approx. 85g)

※In case of the AC voltage model, SSR drive output method (standard ON/OFF control, cycle, control, phase control) is available to select.
※Display accuracy: Thermocouple L(IC) type, RTD Cu50Ω
•At room temperature (23℃ ±5℃): (PV ±0.5% or ±2℃, select the higher one) ±1-digit
•Out of room temperature range: (PV ±0.5% or ±3℃, select the higher one) ±1digit
In case of TC4SP Series, ±1℃ will be added.
※The weight includes packaging. The weight in parenthesis is for unit only.
※Environment resistance is rated at no freezing or condensation.

 

Temperature Controller
Type Economical Single Display
Power Supply 110 – 220 VAC
Dimensions 72 x 36 mm
Control Output Relay+SSR(AC/DC power), Relay+SSRP(AC power)
Alarm Output Alarm1