Temperature Controller 48×48 – TK4S-14RN

TEMP.CONTROLER.PID RELAY 48X48

Display method 4-digit 7-segment LED
Control method ON/OFF control, P, PI, PD, PID control
Input specification Thermocouple: K(CA), J(IC), E(CR), T(CC), B(PR), R(PR), S(PR), N(NN), C(TT), G(TT), L(IC), U(CC), Platinel II
RTD: DPt100Ω, DPt50Ω, JPt100Ω, Cu100Ω, Cu50Ω, Nikel 120Ω
Analog: 0-100mV, 0-5V, 1-5V, 0-10V
0-20mA, 4-20mA
Sampling cycle 50ms
Control output 1 Relay(250VAC~ 3A)
Option input CT, Digital(DI-1)
Option output Alarm 1
Power supply 100-240VAC~ 50/60Hz
Protection structure IP65(front panel)
Display accuracy_RTD •At room temperature(23℃±5℃):(PV ±0.3% or ±1℃, select the higher one) ±1-digit
•Out of room temperature:(PV ±0.5% or ±2℃, select the higher one) ±1-digit
Display accuracy_Thermocouple •At room temperature(23℃±5℃):(PV ±0.3% or ±1℃, select the higher one) ±1-digit
•Out of room temperature:(PV ±0.5% or ±2℃, select the higher one) ±1-digit
Display accuracy_Analog •At room temperature(23℃±5℃): ±0.3% F.S. ±1-digit
•Out of range of room temperature: ±0.5℃% F.S. ±1-digit
Display accuracy_CT input ±5% F.S. ±1-digit
Hysteresis(adjustable sensitivity) RTD/Thermocouples: 1 to 100℃/℉(0.1 to 100.0℃/℉) variable Analog: 1 to 100-digit
Proportional band 0.1 to 999.9℃/℉(0.1 to 999.9%)
Integral time 0 to 9999 sec
Derivative time 0 to 9999 sec
Control period Relay output, SSR drive output: 0.1 to 120.0 sec Current output or SSR drive output selectable: 1.0 to 120.0 sec
Manual reset 0.0 to 100.0%
Environment_Ambient temperature -10 to 50℃, storage: -20 to 60℃
Environment_Ambient humidity 35 to 85% RH, storage: 35 to 85% RH

 

※“S” represents SSR drive output support models which SSRP function (standard ON/OFF control, cycle control, phase control) are available. “C” represents selectable current and SSR drive output support models.
※Select “R” or “C” type in case of using heating&cooling control and “N” type in case of using standard control.
※CT input of TK4N is available only for the standard model which has alarm output 1.
※Display accuracy:
◎At room temperature (23℃±5℃)
• Thermocouple K, J, T, N, E type, below -100℃/Thermocouple L, U, PLⅡ type, RTD Cu50Ω, DPt50Ω: (PV ±0.3% or ±2℃, select the higher one) ±1-digit
• Thermocouple C, G, R, S type, below 200℃: (PV ±0.3% or ±3℃, select the higher one) ±1-digit
• Thermocouple B type, below 400℃: there is no accuracy standards.
◎Out of room temperature range
• RTD Cu50Ω, DPt50Ω: (PV ±0.5% or ±3℃, select the higher one) ±1-digit
• Thermocouple R, S, B, C, G type: (PV ±0.5% or ±5℃, select the higher one) ±1-digit
• Others, Below -100℃: within ±5℃
In case of TK4SP Series, ±1℃ will be added to the degree standard.
※The weight includes packaging. The weight in parenthesis is for unit only.
※Environment resistance is rated at no freezing or condensation.